Can the Westinghouse iGen2200 run GE PWJV10 10,000 Btu/h window air conditioner?

Runs

Runs. Running draw 625 W fits within 1,800 running watts. Startup watts were not published; 2,200 starting watts is at least 3× the running draw, the common planning allowance for a compressor or pump start.

Check priceOpens the manufacturer page. No affiliate link is set in links.json.

The comparison

Westinghouse iGen2200GE PWJV10 10,000 Btu/h window air conditioner
Running watts1,800 W625 W
Starting / surge watts2,200 WNot published
Typeinverter, GasolineCooling
Published runtimeUp to 12 hr at 25% load
SourcesGenerator sourceAppliance source

Questions

Can the Westinghouse iGen2200 run GE PWJV10 10,000 Btu/h window air conditioner?

Runs. Running draw 625 W fits within 1,800 running watts. Startup watts were not published; 2,200 starting watts is at least 3× the running draw, the common planning allowance for a compressor or pump start.

What watts were compared?

Generator: 1,800 running W and 2,200 starting W on gasoline. Appliance: 625 W running, startup not published.

How long will it run?

Fuel runtime depends on total load. Published runtime: Up to 12 hr at 25% load.

Where did the numbers come from?

Westinghouse product page: 2200 peak / 1800 running; 1.14 gal; up to 12 hr at 25%; 46.3 lb; duplex 5-20R and 2 USB. Older spec sheets list 10 hr at 25%. ENERGY STAR lists model PWJV10W**# at 10,000 Btu/h, CEER 16, and 468.8 kWh/year, with a variable-speed compressor. Rated input is 10,000 ÷ 16 = 625 W. 625 × 750 ÷ 1,000 = 468.75, which rounds to the listed 468.8 kWh. Startup watts are not published.