30 amp inlet

Can the Pulsar G12KBN run a house through a 30 amp inlet?

Runs

Yes, through a 30 A 120/240 V inlet and transfer switch or interlock. Its 120/240V 30A twist-lock outlet can feed both legs. Usable through the inlet: 7,200 W running (the 30 A inlet caps at 7,200 W). The essential-circuit list below needs about 4,440 W running and 6,790 W at the worst start, which fits.

Portable generator plugged into a 30 amp outdoor power inlet on a house during an outage

Typical essential circuits

Essential circuitRunning WStarting WVoltage
Refrigerator7002,200120V
Chest freezer7002,200120V
Furnace blower, 1/2 HP8002,350120V
Sump pump, 1/2 HP1,0502,150120V
Well pump, 1/2 HP1,0002,100240V
LED lights, 10 × 9 W90—120V
TV, router and phone charging100—120V
Total4,440+ 2,350 largest start = 6,790 W peak

Typical planning figures from a published generator wattage chart, not measured from a specific model. Check your appliance nameplates. A 30 A, 240 V inlet can carry at most 30 × 240 = 7,200 W.

Questions

Can the Pulsar G12KBN run a house through a 30 amp inlet?

Yes, through a 30 A 120/240 V inlet and transfer switch or interlock. Its 120/240V 30A twist-lock outlet can feed both legs. Usable through the inlet: 7,200 W running (the 30 A inlet caps at 7,200 W). The essential-circuit list below needs about 4,440 W running and 6,790 W at the worst start, which fits.

What does a 30 amp inlet supply?

A 30 A, 120/240 V inlet (L14-30) can carry at most 7,200 W, split across two 120 V legs of 3,600 W each. It only powers the circuits your transfer switch or interlock connects.

Do I need an electrician?

Yes. A transfer switch or listed interlock and inlet box must be installed by a licensed electrician. Never backfeed through a wall outlet.

Safety first

More on the Pulsar G12KBN · What size generator for a 30 amp inlet